Incident response on call, 24/7: +385 98 1900 984NewIR Retainer: a team on contract before an attack
HR · EN
High 8.8actively exploitedCVE-2023-25914

Danfoss AK-SM800A – authenticated path traversal via XML interface

Published 21/08/2023 · Updated 25/11/2026 · Danfoss AK-SM800A

Summary

Danfoss AK-SM800A versions prior to 3.3 improperly restrict file paths in the XML interface (CWE-22, path traversal). An authenticated attacker can retrieve and read system files of the underlying server. According to the advisory, the information that can be read can lead to a full system compromise.

The CVSS 3.1 score is 8.8 (High). The attack is carried out over the network with low complexity and requires only a low-privileged account, with no user interaction. A successful attack can severely impact confidentiality, integrity and availability.

The vulnerability is listed in the CISA KEV catalog (added 2026-11-25, due 2026-11-28), which means it is being actively exploited. Remediation is urgent. The EPSS score is about 1.1% (64th percentile).

Who is affected

Organizations running Danfoss AK-SM800A monitoring and control systems (e.g. for refrigeration) with software versions below 3.3.

What to do

  1. Urgently upgrade all AK-SM800A devices to version 3.3, which the vendor identifies as the patch.
  2. Inventory all AK-SM800A devices and check their software version. All versions prior to 3.3 are affected.
  3. Check whether the device's XML/web interface is reachable from the internet. If it is, restrict access to VPN or trusted networks.
  4. Because the vulnerability is actively exploited, review user accounts and access logs, rotate credentials and look for signs of compromise. If mitigations cannot be applied, follow CISA BOD 26-04 guidance or discontinue use of the product.
  5. For details, see the DIVD advisories (csirt.divd.nl/CVE-2023-25914 and DIVD-2023-00025) and the vendor's official advisory.

Actively exploited (CISA KEV)

Added to the catalog
25/11/2026
Remediation due (CISA)
28/11/2026
Required action
Apply mitigations in accordance with vendor instructions, ensuring compliance with CISA’s BOD 26-04 Prioritizing Security Updates Based on Risk (see URL in Notes) guidance and CISA’s “Forensics Triage Requirements” (see URL in Notes). Follow applicable BOD 26-04 guidance for cloud services or discontinue use of the product if mitigations are unavailable. Stakeholders are responsible for evaluating each asset's internet exposure and ensuring adherence to BOD 26-04 patching guidelines.

Vendor workaround

Upgrade to the latest patch, which is version 3.3.

Original text from the vendor's CVE record.

Affected products and versions

Danfoss AK-SM800A< 3.3

CVSS vector, explained

CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H

Attack vector
Network (from the internet)
Attack complexity
Low
Privileges required
Regular user
User interaction
Not required
Scope
Vulnerable component only
Confidentiality
High impact
Integrity
High impact
Availability
High impact

Weakness type (CWE)

  • CWE-22 Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal')

References

Sources: CVE.org (CNA and CISA ADP), CISA KEV, FIRST EPSS. Always check the vendor's official advisory.